How to Operate a Control Panel with a Fire Alarm
18 AFC-600 Operations PN 51033:A 3/8/99
+RZWR5HV
S
RQGWRD)LUH$ODUP
If the control panel indicates a fire alarm, you can do the following:
1. To silence the panel sounder, press the
ALARM
SILENCE
key. The
FIRE
ALARM
LED
and
ALARM
SILENCED
LED light steady.
The control panel sends an Alarm Silenced message to the History buffer and
installed printers, terminal mode LCD-80s, and CRT-2s. Figure 8 shows a sample
Alarm Silenced message.
)LJXUH 6DPSOH $ODUP 6LOHQFHG 0HVVDJH
2. Check the Alarm message for the location and type of trouble.
3. Correct the condition causing the alarm.
4. When you finish correcting the alarm condition, press the
SYSTEM
RESET
key to
return the control panel to normal operation (indicated by the All Systems
Normal message). The control panel sends an All Systems Normal message to
the LCD display, History buffer, and installed printers, terminal mode LCD-80s,
and CRT-2s.
+RZWR,QWHU
S
UHW)LUH$ODUP7
\S
H&RGHV
The Type Code that displays in the Alarm message indicates the function of the point
that initiates the fire alarm. For example, a monitor module with a
PULL
STATION
Type
Code means that the monitor module connects to a manual pull station. Table 6 contains
a list of the Type Codes that can appear in an alarm message.
7DEOH )LUH $ODUP 7
\S
H &RGHV
Type Code Purpose What if does
MONITOR
(latching)
Activate an alarm-monitoring device Lights
FIRE
ALARM
LED and
activates CBE
PULL
STATION
(latching)
Indicates activation of a manual
fire-activating device, such as a pull
station.
Lights
FIRE
ALARM
LED and
activates CBE
SMOKE
DETECT
(latching)
Indicates activation of a two-wire or
four-wire smoke detector
Lights
FIRE
ALARM
LED and
activates CBE
HEAT
DETECT
(latching)
Indicates activation of a conventional
heat detector
Lights
FIRE
ALARM
LED and
activates CBE
blank
(latching)
Indicates activation of a device with
no description
Lights
FIRE
ALARM
LED and
activates CBE
WATERFLOW
(latching)
Indicates activation a waterflow alarm
switch
Lights
FIRE
ALARM
LED and
activates CBE
MAN
.
RELEASE
(latching)
Indicates activation of a monitor
module programmed to a Releasing
Zone to perform a releasing function
Lights
FIRE
ALARM
LED and
activates CBE
SILENCE
(non-latching)
When an alarm exists, activates the
Alarm Silence function and lights the
ALARM
SILENCED
LED
Lights
ALARM
SILENCED
LED
and activates CBE
6WDWXV EDQQHU
$/$50 6,/(1&('
7LPH DQG GDWH RI WKH $ODUP 6LOHQFHG
$ODUP 6LOHQFHG
$ 78( 
Technical Manuals Online! - http://www.tech-man.com

Table of Contents

Other manuals for Notifier AFC-600

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier AFC-600 and is the answer not in the manual?

Notifier AFC-600 Specifications

General IconGeneral
BrandNotifier
ModelAFC-600
CategoryFire Alarms
LanguageEnglish

Related product manuals