Section 5 Parameters
5-22
Parameters
IS mode (1)
Alarm 1 type
al
Select one of the following nine alarm 1 types:
This parameter is displayed only for models without alarm outputs (i.e.,
models without an alarm mode switch). Settings for models with alarm
outputs are set using the alarm mode switch.
Set
value
Alarm type
Alarm output
operation
0, 9 Alarm function OFF Output OFF
1 Upper- and lower-limit
2 Upper-limit
3 Lower-limit
4
Upper- and lower-limit
range
5
Upper- and lower-limit with
standby sequence
6
Upper-limit with standby
sequence
7
Lower-limit with standby
sequence
8 Absolute-value upper-limit
* Alarm values 1 to 7: Set the deviation from the SP (set point) in the
alarm value (X).
Alarm 8: Set the absolute value from 0°C/°F in the alarm value (Y).
* The default is 2 (upper-limit alarm).
* This parameter is not displayed for models with alarm outputs. The
alarm type can be set for these models using the alarm type switch.
* For models without alarm outputs, this parameter is displayed
regardless of the output assignment setting.
OFF
ON
SP
XX
OFF
ON
SP
XX
ON
OFF
SP
XX
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
SP
X
OFF
ON
Y
Function
Setting