Functions and Operations
5.10 Disabling Cold Junction Compensation
5-31
5.10
Disabling Cold Junction Compensation
This function disables cold junction compensation (terminal
temperature compensation).
Parameter Setting Procedure
Advanced function setting level
Parameter Set value Meaning of set value
Cold junction
compensation
cjc
on Room temperature display
(enabled)
off 0.0
°C (disabled)
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
is displayed on the level/bank
display to indicate the initial setting
level.
B Press the M [MODE] Key several times
to change the PV display to “amov.”
This parameter is not displayed for
the initial status due to setting level
protect.
Refer to "Limiting Key Operations"
(P.5-102) for information on removing
setting level protect.
C Press the S [SHIFT] Key to make the
SV display flash.
The setting can be changed when the
SV display starts to flash.
D Use the U [UP] and S [SHIFT] Keys
to set the password “-0169.” Press the
M [MODE] Key to move to the
advanced function setting level.
•“
L f” is displayed on the level/bank
display to indicate the advanced
function setting level.
E Press the M [MODE] Key several times
to change the PV display to “cjc.”
H
cjc
L f
(CJC)
L
Displays “L 0.”
L 0
M
amov
0
L 0
S
amov
00000
L 0
SU
M
init
Displays “L f.”
off
L f
M
cjc
on
L f