Initialization
Section 4 Initial Setup
4-2
4.1 K3HB-X Initial Setup Example (K3HB-XVD)
The initial setup is explained in the following example.
Settings Example
In the following setting example, 1 to 5-V input is scaled to the range
0.000 to 1.000.
If the measurement value goes above 0.700, comparative output
H turns ON.
If the measurement value goes below 0.500, comparative output L
turns ON.
Initial Setup Flow
Note To change a set value, press the S [SHIFT] Key. (The digit that can be
changed will flash.) Use the S [SHIFT] Key to move to the digit to be
changed, and change the setting using the U [UP] Key.
If the display flashes “s.err” this indicates that the input is outside
the set range, and does not indicate product failure.
Note
1. Move to the initial setting level by pressing the L [LEVEL] Key for at least
3 s (operation will stop).
2. Set input type A “in-ta” to “d vd” and press the M [MODE] Key twice.
1. Set scaling input value A1 “inp.
a1” to1. 0000" and press the M [MODE]
Key.
2. Set scaling display value A1 “dsp.
a1” to 0” and press the M [MODE] Key.
3. Set scaling input value A2inp. a2” to “5. 0000" and press the M [MODE]
Key.
4. Set scaling display value A2dsp. a2” to “1000” and press the M [MODE]
Key.
1. Set the parameter dp to “,,.
,,,” and press the M [MODE] Key.
1.0000 V
5.0000 V
0.000
1.000
0.500
0.700
Display value
Input
value
Comparative output H
Comparative output L
Measurement
value
When the power is turned ON,
a number may be displayed that
is unrelated to the input range
setting.
To display correct values, the
correct input type must be
selected for the wiring.
A Check the wiring and turn the power ON.
Do not change the order of step
B.
When input type A is set, the
scaling value and decimal point
position will be initialized
automatically.
B Set input type A to 1.0000 to 5.0000 V.
C Set the scaling value.
D Set the decimal point position.