EasyManua.ls Logo

Omron K3HB-H - No Output before PASS Range

Omron K3HB-H
226 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions and Operations
5.23 No Output before PASS Range
5-61
5.23 No Output before PASS Range
The standby sequence function can be used to prevent outputs from
turning ON for unstable inputs after the power is turned ON. All outputs
will remain OFF until the measurement value reaches the PASS value.
Parameter Setting Procedure
Advanced function setting level
X V S H
stdby
L f
(STDBY)
ON
All outputs will remain OFF after power is turned ON
until the measurement value reaches the PASS value.
Comparative set value HH/H
Comparative set value LL/L
Output PASS
Output LL/L
Measurement value
OFF
Parameter Set value Meaning of set value
Standby sequence
stdby
on Disabled
off Enabled
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
is displayed on the level/bank
display to indicate the initial setting
level.
B Press the M [MODE] Key several times
to change the PV display to “amov.”
This parameter is not displayed for
the initial status due to setting level
protect.
Refer to "Limiting Key Operations"
(P.5-102) for information on removing
setting level protect.
C Press the S [SHIFT] Key to make the
SV display flash.
The setting can be changed when the
SV display starts to flash.
L
Displays “L 0.”
L 0
M
amov
0
L 0
S
amov
00000
L 0

Table of Contents

Related product manuals