Functions and Operations
5.5 Setting Measurement Operations
5-19
5.5 Setting Measurement Operations
The K3HB has 5 measurement modes, which are set using the
following parameter.
Normal
• Measurement are performed continuously and outputs are based
on comparative results.
• TIMING inputs are ignored.
Important
*
• When the measurement value exceeds the measurement range, a
sensor error will occur and all outputs will turn OFF.
• The measurement value immediately prior to a HOLD input is held
during the HOLD input. Measurements are not performed during
RESET input.
• If RESET and HOLD inputs are competing, the RESET input will
take priority.
The PV display will show “-----” during RESET input (no measurement status).
Selecting operations for input errors
→ P.5-29
Operation will continue if input error enable is set to OFF (disabled) or
OVER (overflow).
Input adjustment level
Parameter Set value Meaning of set value
Timing hold
tmg-h
nomal Normal
s-h Sampling hold
p-h Peak hold
b-h Bottom hold
p-p Peak-to-peak hold
X V S H
tmg-h
L1
(TMG-H)
pplicable models:
K3HB-@@@
+
K35-1
K35-2
K35-3
K35-4
HOLD
RESET
Measurement
value
Power ON
A sensor error occurs and all outputs are turned
OFF if the measurement range is exceeded.
Measurement value N
Measurement
range upper limit
Measurement
value N
MeasuringMeasuringMeasuring
No measurement
Sensor error