Functions and Operations
5.5 Setting Measurement Operations
5-19
5.5 Setting Measurement Operations
The K3HB has 5 measurement modes, which are set using the
following parameter.
Normal
Measurement are performed continuously and outputs are based
on comparative results.
TIMING inputs are ignored.
Important
*
When the measurement value exceeds the measurement range, a
sensor error will occur and all outputs will turn OFF.
The measurement value immediately prior to a HOLD input is held
during the HOLD input. Measurements are not performed during
RESET input.
If RESET and HOLD inputs are competing, the RESET input will
take priority.
The PV display will show-----” during RESET input (no measurement status).
Selecting operations for input errors
P.5-29
Operation will continue if input error enable is set to OFF (disabled) or
OVER (overflow).
Input adjustment level
Parameter Set value Meaning of set value
Timing hold
tmg-h
nomal Normal
s-h Sampling hold
p-h Peak hold
b-h Bottom hold
p-p Peak-to-peak hold
X V S H
tmg-h
L1
(TMG-H)
A
pplicable models:
K3HB-@@@
+
K35-1
K35-2
K35-3
K35-4
HOLD
RESET
Measurement
value
Power ON
A sensor error occurs and all outputs are turned
OFF if the measurement range is exceeded.
Measurement value N
Measurement
range upper limit
Measurement
value N
MeasuringMeasuringMeasuring
No measurement
Sensor error
Remarks