EasyManua.ls Logo

Omron K3HB-H - 4.2 K3 HB-V Initial Setup Example (K3 HB-VLC)

Omron K3HB-H
226 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Initialization
Section 4 Initial Setup
4-4
4.2 K3HB-V Initial Setup Example (K3HB-VLC)
The initial setup is explained in the following example.
Settings Example
Indicated as 0 to 1N in the load cell specifications (rated load 1N,
recommended applied voltage 10 V, rated output 2 mV/V *)
If the measurement value goes above 0.700, comparative output
H turns ON.
If the measurement value goes below 0.500, comparative output L
turns ON.
* 2 mV/V indicates a load cell output of 2 mV for 1 V applied voltage
for the rated load (when using a load of 1 N). When the applied
voltage is 10 V, the load cell output is 20 mV (2 mV
×10)
Initial Setup Flow
Note
To change a set value, press the S [SHIFT] Key. (The digit that can be
changed will flash.) Use the S [SHIFT] Key to move to the digit to be
changed, and change the setting using the U [UP] Key.
If the display flashes “
s. err” this indicates that the input is outside
the set range, and does not indicate product failure.
Note
1. Move to the initial setting level by pressing the L [LEVEL] Key for at least
3 s (operation will stop).
2. Set input type A “in-ta” to “b lc” and press the
M [MODE] Key twice.
+10V
IN
+IN
0V
OUT
OUT
BE
+
Load cell
0.500
0.700
0.000 mV
19.999 mV
1.000
0.000
Display value
Input
value
Comparative output H
Comparative output L
Measurement
value
When the power is turned ON,
a number may be displayed that
is unrelated to the input range
setting.
To display correct values, the
correct input type must be
selected for the wiring.
A Check the wiring and turn the power ON.
Do not change the order of step
B.
When input type A is set, the
scaling value and decimal point
position will be initialized
automatically.
B Set input type A to 0.000 to 19.999 mV.

Table of Contents

Related product manuals