Functions and Operations
5.20 Holding Comparative Outputs
5-55
5.20 Holding Comparative Outputs
The comparative output hold function holds the status of all outputs
after any output except for the PASS output turns ON, i.e., it stops
refreshing outputs. You can choose to stop outputs and continue
measurement, or to stop both.
Outputs will be refreshed again after the reset operation.
• Resetting measurements
→ P.5-26
● Example with Output Refresh Stop ON
Parameter Setting Procedure
Advanced function setting level
Parameter Set value
Meaning of set value
Outputs Measurement
Output refresh stop
o-stp
on Continue Continue
off Stop Continue
all Stop Stop
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•
“
L
0
” is displayed on the level/bank
display to indicate the initial setting level.
B Press the M [MODE] Key several times
to change the PV display to “amov.”
•
This parameter is not displayed for the
initial status due to setting level protect.
Refer to "Limiting Key Operations" (P.5-
102) for information on removing setting
level protect.
X V S H
o-stp
L f
(O-STP)
RESET
Comparative
set value H
Comparative
set value HH
Comparative
set value L
Does not turn ON.
Output L
Output HH
Output H
L
Displays “L 0.”
L 0
M
amov
0
L 0