Functions and Operations
5.34 Using the Position Meter
5-85
5.34 Using the Position Meter
The meter on the right side of the front panel with 20 sections is called
the “position meter” and shows the position of the displayed value
(present value, maximum, or minimum) in relation to any values set
using the position meter upper and lower limits. The position meter
upper and lower limits can be set to any range.
The position meter display pattern is set using the following parameter.
*1. The decimal point depends on the “decimal point position”
parameter setting.
*2. The amount that the displayed value differs from the mid-point
between the position meter upper and lower limits (the deviation) is
displayed.
* If the position meter lower limit set value is smaller than the position
meter upper limit set value, the top and bottom of the above displays
will be reversed.
* The position meter will not be lit if there is an input error.
Display adjustment level
Parameter Set value Meaning of set value
Position meter type
pos-t
off OFF
inc Incremental
inc-r Incremental (reversed)
dev Deviation (*2)
dev-r Deviation (reversed)
Position meter upper limit
pos-h
-19999 to
99999
-19999 to 99999 (*1)
Position meter lower limit
pos-l
-19999 to
99999
-19999 to 99999 (*1)
Position meter
type
Incremental
Incremental
(reversed)
Deviation
Deviation
(reversed)
Position meter
upper limit
(100)
Position meter
lower limit
(0)
X V S H
pos-t
L 2
(POS-T)
pos-l
L 2
(POS-L)
pos-h
L 2
(POS-H)
Present value: 70
DecreaseIncrease Present value
Present value: 70
DecreaseIncrease Present value
DecreaseIncrease Present value
Present value: 85 Present value: 85
DecreaseIncrease Present value