Functions and Operations
Section 5 Functions and Operations
5-86
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
”
is displayed on the level/bank
display to indicate the initial setting
level.
B Press the L [LEVEL] Key several
times to move to the display adjustment
level.
•“
L 2” is displayed on the level/bank
display to indicate the display
adjustment level.
C Press the M [MODE] Key several times
to change the PV display to “pos-t.”
D Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
E Use the U [UP] Key to change the
position meter type setting.
F Press the M [MODE] Key to switch to
the next parameter “pos-h.”
• The parameter for position meter type
is registered.
G Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
H Use the U [UP] and S [SHIFT] Keys
to change the position meter upper limit
setting.
I Press the M [MODE] Key to switch to
the next parameter “pos-l.”
• The parameter for the position meter
upper limit is registered.
L
Displays “L 0.”
L 0
L
sv. dsp
off
Displays “L 2."
L 2
M
pos-t
inc
L 2
S
pos-t
inc
L 2
U
der
L 2
pos-t
M
pos-h
99999
L 2
S
pos-h
99999
L 2
SU
10000
L 2
pos-h
M
pos-l
-19999
L 2