Functions and Operations
5.21 Allocating Another Output to PASS Output
5-57
5.21 Allocating Another Output to PASS Output
The “PASS output change” parameter can be set to output a
comparative output or error output from the PASS output terminal
instead of outputting the PASS output. This function is valid only when
there is a PASS output terminal.
In the default settings, PASS signals are output from the PASS output
terminal.
* The output turns ON when an input error occurs. To allocate input
errors to the PASS output, set the “input error enable” parameter to
s.err. If input error enable is set to off or over, there is no output
because there is no input error.
Setting the “operation at input error” parameter to s.err
P.5-29
* If err is allocated, P will light when err is displayed.
Parameter Setting Procedure
Advanced function setting level
Parameter Set value Meaning of set value
PASS output change
pass
ll LL
l L
pass PAS S
h H
hh HH
err Input error*
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
L
0
” is displayed on the level/bank
display to indicate the initial setting level.
B Press the M [MODE] Key several times
to change the PV display to “amov.”
This parameter is not displayed for the
initial status due to setting level protect.
Refer to "Limiting Key Operations" (P.5-
102) for information on removing setting
level protect.
C Press the S [SHIFT] Key to make the
SV display flash.
The setting can be changed when the
SV display starts to flash.
X V S H
pass
L f
(PASS)
L
Displays “L 0.”
L 0
M
amov
0
L 0
S
amov
00000
L 0