Functions and Operations
Section 5 Functions and Operations
5-58
D Use the U [UP] and S [SHIFT] Keys
to set the password “-0169.” Press the
M [MODE] Key to move to the
advanced function setting level.
•“
L f” is displayed on the level/bank
display to indicate the advanced
function setting level.
E Press the M [MODE] Key to change
the PV display to “pass.”
F Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
G Use the U [UP] Key to change the set
value.
H Press the M [MODE] Key to switch to
the next parameter.
• The set value is registered.
I Press the L [LEVEL] Key for at least
1 s to return to the initial setting level.
1 s min.
J Press the L [LEVEL] Key for at least
1 s to return to RUN level.
1 s min.
SU
M
init
Displays “L f.”
off
L f
M
pass
pass
L f
S
pass
pass
L f
U
pass
h
L f
M
hys
1
L f
L
L 0
L
123. 4
123. 4