EasyManua.ls Logo

Omron K3HB-H - Section 3 Basic Application Methods; Monitoring Tank Levels

Omron K3HB-H
226 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Basic Application Methods
Section 3 Basic Application Methods
3-2
3.1
Monitoring Tank Levels
Advantages of Using the K3HB-X
The tank level can be monitored
The distance to the surface of the liquid can be detected using an
E4PA-LS400-M1 Ultrasonic Displacement Sensor (Sonic
Displacement Sensor).
The liquid volume can be displayed on the K3HB-X to indicate
volume in liters (@@ l). The tank level can also be shown using the
20-section display on the position meter (provides a full-scale level
display).
The number of measurements to be averaged (averaging times)
can be set to 4 to ensure stable readings of levels in relation to full
scale.
Comparative outputs can be generated for tank volume on four
levels: dry tank alarm, lower limit alarm, upper limit alarm, and full
tank alarm.
The display can be forcibly shifted to 0 for readings less than zero
or readings outside the detection range of the Ultrasonic
Displacement Sensor.

Table of Contents

Related product manuals