5.37 Performing Output Tests
The output test function is used to set test measurement values using
the keys to check the comparative outputs against the set comparative
set values.
A test measurement value is set using the following parameter.
Parameter Setting Procedure
Output test level
Parameter Set value Meaning of set value
Te st i n p u t
off Output test disabled
-19999 to
99999
-19999 to 99999
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
is displayed on the level/bank
display to indicate the initial setting
level.
B Press the L [LEVEL] Key several
times to move to the output test level
test.”
•“
L t” is displayed on the level/bank
display to indicate the output test
level.
C Press the S [SHIFT] Key.
The test input will be 0 after moving
to output test status.
D Use the U [UP] and S [SHIFT] Keys
to change the set value.
Use the U [UP] Key to increase the
set value.
Use the S [SHIFT] Key to decrease
the set value.
Continue pressing the key to quickly
increase or decrease the set value.
E Once the output test has finished,
press the L [LEVEL] Key for at least
1 s to return to RUN level.
1 s min.
X V S H
test
L t
(TEST)
L
Displays “L 0.”
L 0
L
test
off
Displays “L t.”
L t
S
test
0
L t
SU
test
1234
L t
L
123. 4
123. 4