Basic Application Methods
Section 3 Basic Application Methods
3-6
3.2
Monitoring Motor Load Current
Advantages of Using the K3HB-X
The motor load current can be monitored and the measurement
value and output status held when the motor is tripped. The
K3HB-X will hold this status even if a power interruption occurs.
A 75:5 current transformer (CT) can be used for motor current
detection.
Up to 10 A can be input directly using the K3HB-XAA.
Current can be displayed in amperes (A) up to two digits past the
decimal point (@@.@@ A) on the K3HB-XAA.
Two-level output detection can be used for the upper limit.
The startup compensation timer on the K3HB-XAA can be set to
prohibit measurements for a certain amount of time after the
motor startup signal is received to prevent judgments that result in
inadvertent output due to inrush current measured when the
motor starts.
The startup compensation timer is set to 10 s.
An output is generated when the H and L values exceed the
comparative output settings. (Uses two-level detection for the
upper limit.)
K3HB-X
Power
supply
ON
signal
Magnetic
relay
0 to 50 A AC
0 to 5 A
Process Indicator
K3HB-XAA
Comparative output 1
(comparative output H)
Comparative output 2
(comparative output L)
Motor
Comparative output H
Startup compensation
timer input
Power supply side
Com
p
arative out
p
ut L
Connections Diagram
100 to 240 VAC
24 VAC/DC
CT
75:5