Functions and Operations
5.9 Selecting Operations for Input Errors
5-29
5.9
Selecting Operations for Input Errors
The display and operation when the input is exceeding input range can
be selected by setting this parameter.
(Refer to "Input Characteristics" (P.A-6) for input ranges.)
Each operation is outlined below.
● Disabled
● Overflow
● Input error
* The errors are “a.err” or “b.err” for the K3HB-S and “s.err” for the
K3HB-X/V/H.
Parameter Setting Procedure
Advanced function setting level
Parameter Set value Meaning of set value
Operation at
input error
s.err
off Disabled
over Overflow
s.err Input error
Display Outputs
The display is fixed at the
measurement value that
corresponds to the upper or lower
limit of the input range. (The display
doesn't flash.)
Outputs correspond to the
fixed display value.
Display Outputs
The display is fixed and flashes at
the measurement value that
corresponds to the upper or lower
limit of the input range.
Outputs correspond to the
fixed display value.
Display Outputs
Error display flashes* All outputs are turned OFF.
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
”
is displayed on the level/bank
display to indicate the initial setting
level.
s. err
L f
(S.ERR)
X V S H
L
Displays “L 0.”
L 0