Initialization
Section 4 Initial Setup
4-6
4.3 K3HB-H Initial Setup Example (K3HB-HTA)
The initial setup is explained in the following example.
Settings Example
Using the K thermocouple (-200.0 to 1300.0
°C) to measure the
temperature, and display in
°C.
• If the measurement value goes 500
°C or higher, comparative
output H turns ON.
• If the measurement value goes 100
°C or lower, comparative
output L turns ON.
Initial Setup Flow
To change a set value, press the S [SHIFT] Key. (The digit that can be
changed will flash.) Use the S [SHIFT] Key to move to the digit to be
changed, and change the setting using the U [UP] Key.
● Note ●
• If the display flashes “
s. err” this indicates that the input is outside
the set range, and does not indicate product failure.
1. Move to the initial setting level by pressing the L [LEVEL] Key for at least
3 s (operation will stop).
2. Set input type A “in-ta” to “2-k” and press the
M [MODE] Key twice.
• Set the temperature unit “d-u” to “c” and press the M [MODE] Key.
1. Return to the RUN level by pressing the L [LEVEL] Key for at least 1 s.
(Start operation.)
2. Press the M [MODE] Key repeatedly until the SV display status shows
.
3. Set the value to “500.
0" and press the M [MODE] Key. (The SV display
status will show .)
4. Set the value to “100.
0" and press the M [MODE] Key. The setting
procedure is completed.
1. Press the M [MODE] Key repeatedly to display the measurement values
and start actual operation.
100.0
500.0
Measurement
value
Comparative output H
Comparative output L
When the power is turned ON,
a number may be displayed that
is unrelated to the input range
setting.
To display correct values, the
correct input type must be
selected for the wiring.
A Check the wiring and turn the power ON.
B Set input type A to K thermocouple (-200.0 to 1300.0°C).
C Set the temperature unit.
D Set comparative set value H to 500.0 and set comparative set
value L to 100.0.
E Start actual operation.
H
L