Functions and Operations
5.8 Not Performing Measurements for Set Intervals
5-27
5.8 Not Performing Measurements for Set Intervals
With this function measurement is not performed until a set time has
passed after the S-TMR input turns ON. (Timing starts at the rising
edge of the S-TMR input and the PV display is “-----” while no
measurement has been performed.)
If the power is turned ON while the s-tmr input is ON, measurement
will not start until the time set in the s-tmr elapses.
This can be used when detecting motor overloads or to ignore motor
inrush currents.
Parameter Setting Procedure
Advanced function setting level
Parameter
Set value
Meaning of set value
Startup compensation timer
s-tmr
0. 0
Startup compensation timer disabled
0.
.1
to
99.
9
0.1 to 99.9 s
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
L
0
” is displayed on the level/bank
display to indicate the initial setting level.
B Press the M [MODE] Key several times
to change the PV display to “amov.”
This parameter is not displayed for the
initial status due to setting level protect.
Refer to "Limiting Key Operations" (P.5-
102) for information on removing setting
level protect.
C Press the S [SHIFT] Key to make the
SV display flash.
The setting can be changed when the
SV display starts to flash.
D Use the U [UP] and S [SHIFT] Keys
to set the password “-0169.” Press the
M [MODE] Key to move to the
advanced function setting level.
•“
L f” is displayed on the level/bank
display to indicate the advanced
function setting level.
E Press the M [MODE] Key several times
to change the PV display to “s-tmr.”
X V S H
s-tmr
L f
(S-TMR)
L
Displays “L 0.”
L 0
M
amov
0
L 0
S
amov
00000
L 0
SU
M
init
Displays “L f.”
off
L f
M
s-tmr
0. 0
L f