Functions and Operations
Section 5 Functions and Operations
5-18
5.4 Setting the Temperature Unit
Either ºC or ºF can be set as the temperature unit.
Parameter Setting Procedure
Initial setting level
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•
“
L
0
”
is displayed on the level/bank
display to indicate the initial setting
level.
B Press the M [MODE] Key several times
to change the PV display to “d-u.”
C Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV starts to flash.
D Press the U [UP] Key to select °C or
°F.
•“c”:
°C, “f”: °F
E Press the L [LEVEL] for at least 1 s to
return to RUN level.
1 s min.
H
L
in-ta
Displays “L 0.”
L 0
M
d-u
c
L 0
U
d-u
c
L 0
S
d-u
c
L 0
L
25. 0
0. 0
L 0