Functions and Operations
5.2 Setting Input Types
5-11
5.2 Setting Input Types
K3HB-X Set the input type to match the connected input device.
* Eliminates inductive noise from the power supply line. Set to the
power supply frequency.
K3HB-V
* Eliminates inductive noise from the power supply line. Set to the
power supply frequency.
Initial setting level
X V S H
Parameter Set value Meaning of set value
DC voltage (XVD)
Input type A
in-ta
a vd ±199.99 V
b vd ±19.999 V
c vd ±1.9999 V
d vd 1.0000 to 5.0000 V
DC current (XAD)
Input type A
in-ta
a ad ±199.99 mA
b ad ±19.999 mA
c ad ±1.9999 mA
d ad 4.000 to 20.000 mA
AC voltage (XVA)
Input type A
in-ta
a va 0.0 to 400.0 V
b va 0.00 to 199.99 V
c va 0.000 to 19.999 V
d va 0.0000 to 1.9999 V
AC current (XAA)
Input type A
in-ta
a aa 0.000 to 10.000 A
b aa 0.0000 to 1.9999 A
c aa 0.00 to 199.99 mA
d aa 0.000 to 19.999 mA
Power supply
frequency*
fre
50 50 Hz
60 60 Hz
in-ta
L 0
(IN-TA)
fre
L 0
(FRE)
Parameter Set value Meaning of set value
Input type A
in-ta
a lc 0.000 to 199.99 mV
b lc 0.000 to 19.999 mV
c lc ±100.00 mV
d lc ±199.99 mV
Power supply
frequency*
fre
50 50 Hz
60 60 Hz
in-ta
L 0
(IN-TA)
fre
L 0
(FRE)

Table of Contents