Functions and Operations
Section 5 Functions and Operations
5-12
K3HB-S
* Make sure the terminal wiring is correct for the input range.
Otherwise, correct values will not be displayed.
K3HB-H
* Eliminates inductive noise from the power supply line. Set to the
power supply frequency.
Parameter Setting Procedure: Input Type
The following procedure uses the K3HB-S as an example.
Parameter Set value Meaning of set value
Input type A
in-ta
or
Input type A
in-tb
0-20 0.000 to 20.000 mA
4-20 4.000 to 20.000 mA
0-5 0.000 to 5.000 V
1-5 1.000 to 5.000 V
5 ±5.000 V
10 ±10.000 V
in-ta
L 0
(IN-TA)
in-tb
L 0
(IN-TB)
Parameter Set value
Meaning of set value
°C °F
Input type A
in-ta
0-pt
−200.0 to 850.0 −300.0 to 1500.0
1-pt
−150.00 to 150.00 −199.99 to 300.00
2-k
−200.0 to 1300.0 −300.0 to 2300.0
3-k
−20.0 to 500.0 0.0 to 900.0
4-j
−100.0 to 850.0 −100.0 to 1500.0
5-j
−20.0 to 400.0 0.0 to 750.0
6-t
−200.0 to 400.0 −300.0 to 700.0
7-e 0.0 to 600.0 0.0 to 1100.0
8-l
−100 to 850.0 −100.0 to 1500.0
9-u
−200.0 to 400.0 −300.0 to 700.0
10-n
−200.0 to 1300.0 −300.0 to 2300.0
11-r 0.0 to 1700.0 0.0 to 3000.0
12-s 0.0 to 1700.0 0.0 to 3000.0
13-b 100.0 to 1800.0 300.0 to 3200.0
14-w 0.0 to 2300.0 0.0 to 4100.0
Power supply
frequency*
fre
50 50 Hz
60 60 Hz
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
”
is displayed on the level/bank
display to indicate the initial setting
level.
in-ta
L 0
(IN-TA)
L 0
fre
(FRE)
L
cal
L 0
Displays “L 0.”
0