Functions and Operations
5.2 Setting Input Types
5-13
Parameter Setting Procedure: Power Supply Frequency*
Set the input type for the K3HB-X/V/H and then set the power supply
frequency.
Perform step E above and then perform the following steps.
B If the PV display is not “in-ta” or “in-
tb,” press the M [MODE] Key to
display the desired parameter.
C Press the S [SHIFT] Key to make the
SV display flash.
The setting can be changed when the
SV display starts to flash.
D Use the U [UP] Key to change the set
value.
E Press the M [MODE] Key to switch to
the next parameter.
The set value is registered.
F Press the L [LEVEL] Key for at least
1 s to return to the RUN level.
1 s min.
* If input type A is changed, scaling input values A1 and A2 and scaling display values A1 and
A2 are initialized. The same applies to input type B.
** Input type A is the only choice for all models except the K3HB-S.
G Press the M [MODE] Key several times
to change the PV display to “fre.”
H Press the S [SHIFT] Key to make the
SV display flash.
The setting can be changed when the
SV starts to flash.
Set the frequency to 50 Hz or 60 Hz
to match the local frequency.
M
in-ta
4-20
L 0
S
in-ta
4-20
L 0
U
in-ta
1-5
M
inp. a1
L
1234. 5
1234. 5
L
fre
50
L 0
L
fre
50
L 0