Appendices
Appendices
A-12
Parameter List
Enter the set value before using.
Level Parameter name Characters Setting range Characters Initial value Decimal point Unit Set
value
---
Version --- --- --- --- --- ---
Status --- --- --- --- --- ---
Measurement value --- −19999 to 99999 --- --- --- EU
Max. value --- −19999 to 99999 --- --- --- EU
Min. value --- −19999 to 99999 --- --- --- EU
Protect
RUN/adjustment
protect
run.pt 0 to 2 0 to 20--- ---
Setting level protect set.pt 0 to 2 0 to 21--- ---
Setting change
protect
wt.pt OFF, ON off, on off --- ---
Forced-zero protect zr.pt OFF, ON off, on off --- ---
Max/Min protect mmpt 0 to 2 0 to 20--- ---
RUN
Measurement value --- −19999 to 99999 -19999 to 99999 --- Conforms to decimal
point position.
EU
Forced-zero status --- OFF, ON --- (Not displayed.) off --- ---
Forced-zero value --- --- --- (Not displayed.) 0 Conforms to decimal
point position.
EU
Tare zero status --- OFF, ON --- (Not displayed.) off --- ---
Tare zero value --- --- --- (Not displayed.) 0 Conforms to decimal
point position.
EU
Measurement value/
comparative set value
HH
--- −19999 to 99999 -19999 to 99999 99999 Conforms to decimal
point position.
EU
Measurement value/
comparative set value
H
--- −19999 to 99999 -19999 to 99999 99999 Conforms to decimal
point position.
EU
Measurement value/
comparative set value
L
--- −19999 to 99999 -19999 to 99999 -19999 Conforms to decimal
point position.
EU
Measurement value/
comparative set value
LL
--- −19999 to 99999 -19999 to 99999 -19999 Conforms to decimal
point position.
EU
Adjustment
Bank bank 0 to 7 0 to 70--- ---
Communication write cmwt OFF, ON off, on off --- ---