Basic Application Methods
3.2 Monitoring Motor Load Current
3-7
Comparative set value H is 50.00 A and comparative set value L is
40.00 A.
RUN Level
Check on the status displays.
Initial Setting Level (L 0) The Setting Level Protect setting must be set to 0 (SET.PT = 0) to
enable moving to the advanced function setting level.
ON
OFF
50.00 A
40.00 A
Comparative set value H
Comparative set value L
Output H
Output PASS
Output L
Display
High
Low
Level output
Parameter
Characters
Set value Remarks
Comparative
set value H
50.
00 Control example for the
following settings:
Comparative output 1:
50.00 A
Comparative output 2:
40.00 A
Comparative
set value L
40.
00
Parameter
Characters
Set value Remarks
Input type A in-ta a aa
Scaling input
value A1
inp.
a10. 000
Scaling display
value A1
dsp. a10
Scaling input
value A2
inp.
a2 5. 000
Scaling display
value A2
dsp. a2 7500
Decimal point
position
dp ,,,.
,,
Comparative
output pattern
out-p level Level output
Move to
advanced
function
setting level
amov -0169 Move to advanced
function setting level to
set the startup
compensation timer
K3HB-XAA
input
Display value: CT primary current
75.00 A
0.00 A
0.000 A
5.000 A