Functions and Operations
5.15 Changing Comparative Output Patterns
5-45
Parameter Setting Procedure
Preventing output chattering → P.5-46
Delaying output OFF timing
→ P.5-52
Outputting at set intervals
→ P.5-49
Reversing output logic
→ P.5-59
Holding already output comparative outputs
→ P.5-55
Performing output tests
→ P.5-90
Allocating other outputs to PASS output
→ P.5-57
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
”
is displayed on the level/bank
display to indicate the initial setting
level.
B Press the M [MODE] Key several times
to change the PV display to “out-p.”
C Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed and the
SV display starts to flash.
D Use the U [UP] Key to change the set
value.
E Press the M [MODE] Key to switch to
the next parameter.
• The set value is registered.
F Press the L [LEVEL] Key for at least
1 s to return to RUN level.
1 s min.
L
Displays “L 0.”
L 0
M
out-p
nomal
L 0
S
out-p
nomal
L 0
U
out-p
zone
L 0
M
L 0
L
123. 4
123. 4
Remarks