Functions and Operations
5.16 Preventing Output Chattering
5-47
Hysteresis is set using the following parameter.
* The decimal point depends on the “decimal point position” setting.
Parameter Setting Procedure
Parameter Set value Meaning of set value
Hysteresis
hys
0 to 9999 0 to 9,999 *
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
”
is displayed on the level/bank
display to indicate the initial setting
level.
B Press the M [MODE] Key several times
to change the PV display to “amov.”
•
This parameter is not displayed for the
initial status due to setting level
protect.
Refer to "Limiting Key Operations"
(P.5-102) for information on removing
setting level protect.
C Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
D Use the U [UP] and S [SHIFT] Keys
to set the password “-0169.” Press the
M [MODE] Key to move to the
advanced function setting level.
•“
L f” is displayed on the level/bank
display to indicate the advanced
function setting level.
E Press the M [MODE] Key several times
to change the PV display to “hys.”
F Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
G Use the U [UP] and S [SHIFT] Keys
to change the set value.
hys
L f
(HYS)
L
Displays “L 0.”
L 0
M
amov
0
L 0
S
00000
L 0
amov
SU
M
init
Displays “L f.”
off
L f
M
hys
1
L f
S
hys
0001
L f
SU
hys
0050
L f