Functions and Operations
Section 5 Functions and Operations
5-64
* If the upper and lower limit are set to the same value, then the upper
limit will equals the lower limit plus 1 for linear output.
* When a linear output is mounted, the “linear current type” or “linear
voltage type” parameter can be set according to the type of linear
output.
Parameter Setting Procedure
Parameter Set value Meaning of set value
Linear current type
lset.c
0-20 0 to 20 mA
4-20 4 to 20 mA
Linear voltage type
lset.v
0-5 0 to 5 V
1-5 1 to 5 V
0-10 0 to 10 V
Linear output upper
limit
lset.h
-19999 to
99999
-19999 to 99999
Linear output lower
limit
lset.l
-19999 to
99999
-19999 to 99999
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
is displayed on the level/bank
display to indicate the initial setting
level.
B Press the L [LEVEL] Key once (less
than 1 s) or several times to move to
the linear output level and display
1set.c.”
•“
L 5" is displayed on the level/bank
display to indicate the linear output
level.
C Press the S [SHIFT] Key to make the
SV display flash.
The setting can be changed when the
SV display starts to flash.
D Use the U [UP] Key to change the set
value.
E Press the M [MODE] Key to switch to
the next parameter.
The set value is registered.
F Press the L [LEVEL] Key for at least
1 s to return to RUN level.
1 s min.
L
Displays “L 0.”
L 0
L
lset. c
0-20
L s
Displays “L s.”
S
0
L s
lset. c
U
4-20
L s
lset. c
M
lset. h
99999
L s
L
123. 4
123. 4