Functions and Operations
Section 5 Functions and Operations
5-76
* Holds values even for no measurement status, an input error, or an
overflow.
* Holds values even with a software reset performed through key
operations or communications.
* The power interruption memory cannot be accessed if the startup
compensation timer is enabled when the power is turned ON.
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•
“
L
0
” is displayed on the level/bank
display to indicate the initial setting level.
B
Press the
L
[LEVEL] Key once (less
than 1 s) to move to the input adjustment
level.
1 s min.
•
“
L
1”
is displayed on the level/bank display
to indicate the input adjustment level.
C Press the M [MODE] Key several times
to change the PV display to “step.”
D Press the S [SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
E Use the U [UP] Key to change the set
value.
F Press the M [MODE] Key to switch to
the next parameter.
• The set value is registered.
G Press the L [LEVEL] Key for at least
1 s to return to RUN level.
1 s min.
OFF ON
Power supply
Held
Reset
Max./Min.
value
L
Displays “L 0.”
L 0
L
tmg-h
nomal
L 1
Displays “L 1."
L
off
L 1
memo
S
off
L 1
memo
U
on
L 1
memo
M
tmg-h
nomal
L 1
L
123. 4
123. 4