A-6
Input Characteristics
K3HB-X
Note: The accuracy is for an input frequency range of 40 Hz to 1 kHz (except for AD current input A and B
ranges) and an ambient temperature of 23 ±5
°C. The error, however, increases below 10% of the
maximum input value.
DC voltage input, all ranges: 10% or less of max. input = ±0.15% FS
DC current input, all ranges: 10% or less of max. input = ±0.1% FS
AC voltage input, 0.0 to 400.0 V: 10% or less of max. input = ±0.15% FS
AC voltage input, 0.00 to 199.99 V: 10% or less of max. input = ±0.2% FS
AC voltage input, 0.000 to 19.999 V or 0.0000 to 1.9999 V: 10% or less of max. input = ±1.0% FS
AC current input, 0.000 to 10.000 A: 10% or less of max. input = ±0.25% FS
AC current input, 0.0000 to 1.9999 A: 10% or less of max. input = ±0.5% FS
AC current input, 0.00 to 199.99 mA or 0.000 to 19.999 A: 10% or less of max. input = ±0.15% FS
K3HB-V
Note: The accuracy is for an ambient temperature of 23 ±5°C. For all ranges,10% or less of max. input =
±0.1% FS.
Input
type
Setting range Specified range Accuracy
DC
voltage
VD
±199.99 V
±19.999 V
±1.9999 V
1.0000 to 5.0000 V
199.99 to 219.99 V
1.999 to 21.999 V
1.9999 to 2.1999 V
0.5000 to 5.5000 V
DC voltage input, all ranges: ±0.1% rdg
±1 dig max.
DC current input, all ranges: ±0.1% rdg
±1 dig max.
AC voltage input, 0.0 to 400.0 V or 0.00 to
199.99 V: ±0.3% rdg ±5 dig max.
AC voltage input, 0.000 to 19.999 V or
0.0000 to 1.9999 V: ±0.5% rdg ±10 dig max.
AC current input, 0.000 to 10.000 A or
0.0000 to 1.9999 A: ±0.5% rdg ±20 dig max.
AC current input, 0.00 to 199.99 mA or
0.000 to 19.999 A: ±0.5% rdg ±10 dig max.
DC
current
AD
±199.99 mA
±19.999 mA
±1.9999 mA
4.000 to 20.000 mA
199.99 to 219.99 mA
19.999 to 21.999 mA
1.9999 to 2.1999 mA
2.000 to 22.000 mA
AC
voltage
VA
0.0 to 400.0 V
0.00 to 199.99 V
0.000 to 19.999 V
0.0000 to 1.9999 V
0.0 to 440.0 V
0.00 to 219.99 V
0.000 to 21.999 V
0.0000 to 1.9999 V
AC
current
AA
0.000 to 10.000 A
0.0000 to 1.9999 A
0.00 to 199.99 mA
0.000 to 19.999 mA
0.000 to 11.000 A
0.0000 to 2.1999 A
0.00 to 219.99 mA
0.000 to 21.999 mA
Input
type
Setting range Specified range Accuracy
A 0.00 to 199.99 mV
19.99 to 219.99 mA
0.00 to 199.99 mV: ±0.1% rdg ±1 dig max.
0.000 to 19.999 mV: ±0.1% rdg ±5 dig max.
±100.00 mV: ±0.1% rdg ±3 dig max.
±199.999 mV: ±0.1% rdg ±1 dig max.
B 0.000 to 19.999 mV
1.999 to 21.999 mA
C ±100.00 mV 110.00 to 110.00 mV
D ±199.999 mV 199.99 to 219.99 mV

Table of Contents