Basic Application Methods
Section 3 Basic Application Methods
3-4
RUN Level
Check on the status displays.
Initial Setting Level (L 0)
Input Adjustment Level
(L 1)
Parameter
Characters
Set
value
Remarks
Comparative
set value HH
3400
Control example for the following
settings:
Full tank alarm set: 3,400 mm
Upper limit alarm: 3,200 mm
Lower limit alarm: 800 mm
Dry tank alarm: 400 mm
Comparative
set value H
3200
Comparative
set value L
800
Comparative
set value LL
400
Parameter
Characters
Set value Remarks
Input type A in-ta d ad
Scaling input
value A1
inp.
a14. 00
Scaling display
value A1
dsp. a1 3500
Scaling input
value A2
inp.
a2 20. 000
Scaling display
value A2
dsp. a2 0
Decimal point
position
dp ,,,,,
Comparative
output pattern
out-p nomal
E4PA-LS400-M1
Output
Measurement distance
3,500 mm
0 mm
4.00 mA
20.00 mA
Parameter
Characters
Set value Remarks
Timing hold tmg-h nomal Normal
Zero-limit z-lim on Enables the zero-limit
function.
Zero-limit value lim-p 0 Displays 0 for values
less than zero.
Averaging type avg-t move Moving average
Averaging
times
avg-n 4
4