Section 3 Basic Application Methods
3-4
RUN Level
✽ Check on the status displays.
Initial Setting Level (L 0)
Input Adjustment Level
(L 1)
Parameter
Characters
Set
value
Remarks
Comparative
set value HH
✽
3400
Control example for the following
settings:
Full tank alarm set: 3,400 mm
Upper limit alarm: 3,200 mm
Lower limit alarm: 800 mm
Dry tank alarm: 400 mm
Comparative
set value H
✽
3200
Comparative
set value L
✽
800
Comparative
set value LL
✽
400
Parameter
Characters
Set value Remarks
Input type A in-ta d ad
Scaling input
value A1
inp.
a14. 00
Scaling display
value A1
dsp. a1 3500
Scaling input
value A2
inp.
a2 20. 000
Scaling display
value A2
dsp. a2 0
Decimal point
position
dp ,,,,,
Comparative
output pattern
out-p nomal
E4PA-LS400-M1
Output
Measurement distance
3,500 mm
0 mm
4.00 mA
20.00 mA
Parameter
Characters
Set value Remarks
Timing hold tmg-h nomal Normal
Zero-limit z-lim on Enables the zero-limit
function.
Zero-limit value lim-p 0 Displays 0 for values
less than zero.
Averaging type avg-t move Moving average
Averaging
times
avg-n 4
4