Functions and Operations
5.6 Shifting the Temperature Input
5-25
Parameter Setting Procedure
A Press the L [LEVEL] Key for at least
3 s in RUN level to move to the initial
setting level.
3 s min.
•“L
0
is displayed on the level/bank
display to indicate the initial setting
level.
B Press the L [LEVEL] Key for less than
1 s in initial setting level to move to the
input adjustment level.
1s max.
•“L 1” is displayed on the level/bank
display to indicate the initial setting
level.
C Press the M [MODE] Key several times
to change the PV display to “ini.
1."
D Press the S [SHIFT] Key to make the
SV display flash.
The setting can be changed when the
SV display starts to flash.
E Use the U [UP] and the S [SHIFT]
Keys to change the set value.
F Press the M [MODE] Key to switch the
PV display to “iss.
1.".
G Repeat steps D through F to set “iss.
1,”isi. 2” and “iss. 2."
L
Displays “L 0.”
L 0
L
L 1
M
isi1
-200. 0
L 1
S
isi1
-200. 0
L 1
SU
isi1
-100. 0
L 1
M
iss1
0. 00
L 1