Functions and Operations
5.26 Setting the Step for Changing the Rightmost Digit
5-63
5.26 Setting the Step for Changing the Rightmost Digit
The step for changing the rightmost digit on the display is set using the
following parameter.
Parameter Setting Procedure
Input adjustment level
Parameter Set value Meaning of set value
Step value
step
off
Refer to the diagram below.
2
5
10
A Press the L[LEVEL] Key for at least 3
s in RUN level to move to the initial
setting level.
3 s min.
•
"
L
0" is displayed on the level/bank
display to indicate the initial setting level.
B
Press the L[LEVEL] Key once (less than
1 s) to move to the input adjustment level.
Less
than 1 s
•
"
L
1
" is displayed on the level/bank display
to indicate the input adjustment level.
C Press the M[MODE] Key several times
to change the PV display to "step".
D Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed and the
SV display starts to flash.
E Use the U[UP] Key to change the set
value.
F Press the M[MODE] Key to switch to
the next parameter.
• The set value is registered.
G Press the L[LEVEL] Key for at least 1
s to return to RUN level.
1 s min.
step
L
1
(STEP)
Display values
for rightmost digit
Measurement value
Set value off
Set value 2
Set value 5
Set value 10
0 1 2 3 4 5 6 7 8 9 10
0 1 2 3 4 5 6 7 8 9 10
100 2 4 6 8
0 5 10
0 10