Functions and Operations
5.17 Holding Already Output Comparative Outputs
5-47
5.17 Holding Already Output Comparative Outputs
Output refresh stop is the function that holds output comparative
outputs. While comparative outputs are being held, the comparative
output status and display color are also held but measurement
continues.
If output refresh stop "o-stp" is ON and a comparative output has
been output, that output is held and subsequent different comparative
outputs and sensor errors are not output.
The reset operation clears output refresh stop.
• Reset operation → P.5-20
● Comparative output example when output refresh stop is ON
Parameter Setting Procedure
Advanced-function setting level
Parameter Set value Meaning of set value
Output refresh stop
o-stp
on Enabled
off Disabled
A Press the L[LEVEL] Key for at least 3
s in RUN level to move to the initial
setting level.
3 s min.
•
"
L
0" is displayed on the level/bank
display to indicate the initial setting level.
B Press the M[MODE] Key several times
to change the PV display to "amov".
•
This parameter is not displayed for the
initial status due to setting level protect.
Refer to "Limiting Key Operations" (P.5-
80) for information on removing setting
level protect.
C Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
o-stp
L
f
(O-STP)
RESET
Comparative
set value H
Comparative
set value HH
Comparative
set value L
Does not turn ON.
Output L
Output HH
Output H
L
cal
0
Displays "
L
0".
L
0
M
amov
0
L
0
S
amov
00000
L
0