Functions and Operations
Section 5 Functions and Operations
5-70
5.30 Forcing Automatic Return to Normal Display
If no key operations are made after switching the display in RUN or
adjustment levels, the display will automatically return to the display
after the power is turned ON. The time until automatic display return
can be set and the automatic display return can be disabled.
Automatic display return settings are made using the following
parameter.
Parameter Setting Procedure
Display adjustment level
Parameter Set value Meaning of set value
Automatic display return
ret
0 to 99 0 to 99 s
Automatic display return will
not occur if set to 0.
A Press the L[LEVEL] Key for at least 3
s in RUN level to move to the initial
setting level.
3 s min.
•"
L
0" is displayed on the level/bank
display to indicate the initial setting
level.
B Press the L[LEVEL] Key several times
to move to the display adjustment level.
•"
L
2" is displayed on the level/bank
display to indicate the display
adjustment level.
C Press the M[MODE] Key several times
to change the PV display to "ret".
D Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
E Use the U[UP] and S[SHIFT] Keys to
change the set value.
F Press the M[MODE] Key to switch to
the next parameter.
• The set value is registered.
G Press the L[LEVEL] Key for at least 1
s to return to RUN level.
1 s min.
ret
L
2
(RET)
L
cal
0
Displays "
L
0".
L
0
L
Displays "
L
2".
L
2
sv. dsp
off
M
ret
10
L
2
S
ret
10
L
2
SU
03
L
2
ret
M
pos-t
inc
L
2
L
123. 4
123. 4