Functions and Operations
5.7 Selecting Operations for Input Errors
5-23
5.7
Selecting Operations for Input Errors
The display and operation when the input is exceeding input range can
be selected by setting this parameter.
(Refer to Input Characteristics in the appendices for input ranges.)
Each operation is outlined below.
●Disabled
●Overflow
●Input error
* When an error occurs for input A or inputs A and B, the display will
show "a.err". When an error occurs for input B, the display will show
"b.err".
Parameter Setting Procedure
Advanced-function setting level
Parameter Set value Meaning of set value
Operation at
input error
s.err
off Disabled
over Overflow
s.err Input error
Display Output
The display is fixed at the
measurement value that
corresponds to the upper or lower
limit of the input range. (The display
doesn't flash.)
Outputs a value that
corresponds to the fixed
display value.
Display Output
The display is fixed at the
measurement value that
corresponds to the upper or lower
limit of the input range and flashes.
Outputs a value that
corresponds to the fixed
display value.
Display Output
Error display flashes * All outputs turned OFF.
A Press the L[LEVEL] Key for at least 3
s in RUN level to move to the initial
setting level.
3 s min.
•"
L
0" is displayed on the level/bank
display to indicate the initial setting
level.
B Press the M[MODE] Key several times
to change the PV display to "amov".
• This parameter is not displayed for
the initial status due to setting level
protect.
Refer to "Limiting Key Operations"
(P.5-80) for information on removing
setting level protect.
s.
err
L
f
(S.ERR)
L
cal
0
Displays "
L
0".
L
0
M
amov
0
L
0