Functions and Operations
Section 5 Functions and Operations
5-16
5.4 Setting Measurement Operations
The K3HB-S has 5 measurement modes, which are set using the
following parameter.
Normal
• Continuously performs measurement and always outputs based
on comparative results.
• TIMING inputs are ignored.
Important
*
• When the measurement value exceeds the measurement range,
a sensor error will occur and all outputs will turn OFF.
• The measurement value immediately prior to a HOLD input is held
during the HOLD input. Measurements are not performed during
RESET input.
• If RESET and HOLD inputs are competing, the RESET input will
take priority.
The PV display will show "-----" in no measurement status.
Selecting operations for input errors. → P.5-23
If the operation at input error is set to OFF (disabled) or OVER
(overflow), operations will continue.
Input adjustment level
Parameter Set value Meaning of set value
Timing hold
tmg-h
nomal Normal
s-h Sampling hold
p-h Peak hold
b-h Bottom hold
p-p Peak-to-peak hold
tmg-h
L
1
(TMG-H)
HOLD
RESET
Measurement
value
Power ON
A sensor error occurs and all outputs are turned
OFF if the measurement range is exceeded.
Measurement value N
Measurement
range upper limit
Measurement
value N
MeasuringMeasuringMeasuring
No measurement
Sensor error
Remarks