EasyManua.ls Logo

Omron K3HB - Delaying Output off Timing

Omron K3HB
150 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions and Operations
Section 5 Functions and Operations
5-44
5.15 Delaying Output OFF Timing
Output OFF delay is the function that delays the OFF timing for
comparative results.
Shot output (shot) is given priority over OFF delay (off-d). OFF
delay will be disabled if shot output is set to anything other than "0",
regardless of the OFF delay setting.
If the measurement value changes and the comparative result that had been ON until now turns OFF, the
comparative output is held for the time set for the output OFF delay parameter.
The comparative output ON time may be shortened if measurement values change quickly. When
comparative output signals are read by external devices, short signals may not be received properly.
In such situations, the output OFF delay can be used to output comparative output signal values for a set
duration or greater.
Output OFF delay is set using the following parameter.
Parameter Setting Procedure
Advanced-function setting level
Explanation of Functions Output OFF delay
Parameter Set value Meaning of set value
Output OFF delay
off-d
0 to 1999 0 to 1,999 ms
A Press the L[LEVEL] Key for at least 3
s in RUN level to move to the initial
setting level.
3 s min.
•"
L
0" is displayed on the level/bank
display to indicate the initial setting
level.
B Press the M[MODE] Key several times
to change the PV display to "amov".
This parameter is not displayed for
the initial status due to setting level
protect.
Refer to "Limiting Key Operations"
(P.5-80) for information on removing
setting level protect.
C Press the S[SHIFT] Key to make the
SV display flash.
The setting can be changed when the
SV display starts to flash.
D Use the U[UP] and S[SHIFT] Keys to
set the password "-0169". Press the
M[MODE] Key to move to the
advanced-function setting level.
•"
L
f" is displayed on the level/bank
display to indicate the advanced-
function setting level.
off-d
L
f
(OFF-D)
L
cal
0
Displays "
L
0".
L
0
M
amov
0
L
0
S
amov
00000
L
0
SU
M
init
Displays "
L
f".
off
L
f

Table of Contents

Other manuals for Omron K3HB