Functions and Operations
5.3 Setting Scaling Values
5-15
Decimal point position
Teaching
Use the teaching function to use real inputs to set scaling input values
"inp.
a1", "inp.
a2", "inp.b1", and "inp.b2".
Parameter Setting Procedure
J Press the M[MODE] Key to switch the
PV display to the next parameter "dp".
K Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV starts to flash.
L Use the U[UP] Key to change the set
value.
M Press the M[MODE] Key to switch to
the next parameter.
• The set value is registered. * The display may be
different.
N Press the L[LEVEL] Key for at least 1
s to return to the RUN level.
1 s min.
M
dp
L
0
,,. ,,,
S
dp
,,. ,,,
L
0
U
dp
,,,.,,
L
0
M
nomal
out-p
L
0
L
1234. 5
1234. 5
After performing step B, press the U[UP]
Key.
• Teaching is enabled and "T" is lit.
• The setting changes to match the
actual input.
Press the U[UP] Key again.
• The input value is registered as the
set value and the monitor mode is
entered.
• Press the M[MODE] Key when in
teaching mode to cancel teaching
and switch to the next parameter.
* Even if a sensor error occurs during
teaching or the U[UP] Key is pressed
when no measurement has been made,
the input value is not registered.
U
inp. a1
10. 412
"T" is lit.
L
0
U
inp. a1
10. 412
"T" changes
from flashing
to being lit.
L
0