Functions and Operations
Section 5 Functions and Operations
5-68
Parameter Setting Procedure
A Press the L[LEVEL] Key for at least 3
s in RUN level to move to the initial
setting level.
3 s min.
•"
L
0" is displayed on the level/bank
display to indicate the initial setting
level.
B Press the L[LEVEL] Key several times
to move to the display adjustment level.
•"
L
2" is displayed on the level/bank
display to indicate the display
adjustment level.
C Press the M[MODE] Key several times
to change the PV display to "pos-t".
D Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
E Use the U[UP] Key to change the
position meter type setting.
F Press the M[MODE] Key to switch to
the next parameter "pos-h".
• The parameter for position meter type
is registered.
G Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
H Use the U[UP] and S[SHIFT] Keys to
change the position meter upper limit
setting.
I Press the M[MODE] Key to switch to
the next parameter "pos-l".
• The parameter for the position meter
upper limit is registered.
J Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
L
cal
0
Displays "
L
0".
L
0
L
sv. dsp
off
Displays "
L
2".
L
2
M
pos-t
inc
L
2
S
pos-t
inc
L
2
U
der
L
2
pos-t
M
pos-h
99999
L
2
S
pos-h
99999
L
2
SU
10000
L
2
pos-h
M
pos-l
-19999
L
2
S
-19999
L
2
pos-l