Specifications
A-3
Characteristics
Sampling period One input: 0.5 ms; Two inputs: 1 ms
Accuracy One input: ±0.1% FS ±1 digit max. (at 23 ± 5 °C)
Two inputs: ±0.2% FS ±1 digit max. (at 23 ± 5 °C)
Display range -19999 to 99999
Comparative output response
time (transistor output)
For one input: OFF ON 1 ms and ON OFF 1.5 ms
For two inputs: OFF ON 2 ms and ON OFF 2.5 ms
Insulation resistance 20 Mmin. (at 500 VDC)
Dielectric strength Between external terminals and case
2,300 VAC for 1 min between external terminals and case
Noise immunity
100 to 240-VAC models: ±1,500 V at power supply terminals in normal or
common mode (waveform with 1-ns rising edge and pulse width of 1
µ
s/100 ns)
24-VAC/VDC models: ±1,500 V at power supply terminals in normal or common
mode (waveform with 1-ns rising edge and pulse width of 1
µ
s/100 ns)
Vibration resistance Frequency: 10 to 55 Hz;
Acceleration: 50 m/s
2
to 10 sweeps of 5 min each in X, Y, and Z directions
Shock resistance 150m/s
2
(100m/s
2
for relay outputs)
3 times each in 3 axes, 6 directions
Weight Approx. 300 g (Linear Sensor Indicator only)
Enclosure rating
Front panel: Conforms to NEMA 4X (equivalent to IP66), Rear case: IP20,
Terminals: IP00 + finger protection (VDE 0106/100)
Memory protection EEPROM (non-volatile memory) Number of rewrites: 100,000 times
Installation environment Overvoltage category II, pollution degree 2 (as per IEC61010-1)
Applicable standards UL3121-1, CSA C22.2 No. 1010.1 (evaluated by UL)
EN61010-1 (IEC61010-1): Pollution degree 2/overvoltage category II
(Evaluated by TUV Product Service.)
EN61326: 1997, A1: 1998, A2: 2001
EMC (EMI) EN61326+A1 Industrial applications
Terminal interference wave
voltage
CISPR 11 Group 1,
Class A: CISPR16-1/-2
Electromagnetic
interference wave
CISPR 11 Group 1,
Class A: CISPR16-1/-2
(EMS) EN61326+A1 Industrial applications
Electrostatic discharge
(ESD)
EN61000-4-2 : 4 kV (contact)
: 8 kV (in air)
Radiating radio-frequency
electromagnetic field
EN61000-4-3: 10 V/m 1 kHz sine wave
amplitude modulation (80 MHz to 1 GHz)
Burst EN61000-4-4 : 2 kV (power line)
: 1 kV (I/O signal line)
Surge EN61000-4-5 : 1 kV with line (power line)
:
2 kV with ground (power line)
Radio-frequency electric
interference
EN61000-4-6: 3 V (0.15 to 80 MHz)
Momentary power
interruptions from voltage dips
EN61000-4-11: 0.5 cycle, 0°, 180°, 100%
(rated voltage)