Functions and Operations
5.10 Averaging Inputs
5-31
Averaging is set using the following parameters.
* To not use averaging, set the average type "avg-t" to smpl and the
averaging times "avg-n" to 1.
Parameter Setting Procedure
Parameter Set value Meaning of set value
Average type
avg-t
smpl Simple average
move Moving average
Averaging times
avg-n
1 1
2 2
4 4
8 8
16 16
32 32
64 64
128 128
256 256
512 512
1024 1024
A Press the L[LEVEL] Key for at least 3
s in RUN level to move to the initial
setting level.
3 s min.
•
"
L
0" is displayed on the level/bank
display to indicate the initial setting level.
B
Press the L[LEVEL] Key once (less than
1 s) to move to the input adjustment level.
Less
than 1 s
•"
L
1" is displayed on the level/bank
display to indicate the input
adjustment level.
C Press the M[MODE] Key several times
to switch the PV display to "avg-t".
D Press the S[SHIFT] Key to make the
SV display flash.
• The setting can be changed when the
SV display starts to flash.
E Use the U[UP] Key to change the
average type setting.
F Press the M[MODE] Key to change to
the next parameter "avg-n".
•
The average type setting is registered.
avg-t
L
1
(AVG-T)
avg-n
L
1
(AVG-N)
L
cal
0
Displays "
L
0".
L
0
L
tmg-h
Displays "
L
1".
nomal
L
1
M
avg-t
smpl
L
1
S
avg-t
smpl
L
1
U
avg-t
move
L
1
M
avg-n
1
L
1