EasyManua.ls Logo

Omron M1 Series - Page 46

Omron M1 Series
808 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
*3. A voltage higher than the power supply voltage cannot be output.
*4. When Carrier Frequency (F26) is set to the following or below, derating is required.
HHD mode...A2001 to A2037: 8 kHz, A2055 to A2185: 10 kHz
HND mode...A2001 to A2037: 4 kHz, A2055 to A2150: 10 kHz, A2185: 4 kHz
For derating, refer to A-1 Derating Table on page A-2.
*5.
The following shows the calculated value when the power supply capacity is 500 kVA (10x the inverter ca-
pacity when the inverter capacity exceeds 50 kVA) and when a %X = 5% power supply is connected.
*6. The numeric value is the average braking torque per individual motor. (Varies according to motor efficiency)
*7. Allowable ambient temperature of 40°C or below of A2022 to A2037 in the HND mode.
The rated output current in the HND mode decreases by 1% for every temperature increase of 1°C when
the ambient temperature is 40°C or more.
Three-phase 400-V Class
HHD/HD: Heavy load, HND/ND: Light load
Item Three-phase 400 V
Model
(3G3M1-A4□□□)
004 007 015 022 030 040 055 075 110 150 185 220
Maxi-
mum
applica-
ble mo-
tor ca-
pacity
*1
kW HD 0.75 1.1 2.2 3 4 5.5 7.5 11 15 18.5 22 30
ND 0.75 1.5 2.2 3 4 5.5 11 15 18.5 22 30 37
HHD 0.4 0.75 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22
HND
0.75 1.1 2.2
3
*7
4
5.5
*7
7.5 11 15 18.5 22 30
HP HD
1
1
1/2
3 4 5
7
1/2
10 15 20 25 30 40
ND
1
1
1/2
3 4 5
7
1/2
15 20 25 30 40 50
HHD
1/2 1
1
1/2
3 4 5
7
1/2
10 15 20 25 30
HND
1
1
1/2
3 4 5
7
1/2
10 15 20 25 30 40
Rated
output
capacity
[kV
A]
*2
380 V HD
1.2 2.2 3.3 4.1 5.8 7.3 12 15 20 25 30 39
ND 1.4 2.7 3.6 4.5 6.1 7.9 14 19 24 29 39 47
HHD 1.2 2.2 3.2 3.6 4.7 6.1 9.7 12 16 20 26 30
HND 1.4 2.7 3.6 4.5 5.8 7.3 12 15 20 25 30 39
480 V HD 1.5 2.8 4.2 5.2 7.3 9.2 15 19 26 32 37 50
ND 1.7 3.4 4.6 5.7 7.6 10 18 24 31 37 49 60
HHD 1.5 2.8 4 4.6 6 7.6 12.3 15 20 26 32 37
HND 1.7 3.4 4.6 5.7 7.3 9.2 15 19 26 32 37 50
Rated input voltage
*3
Three-phase 380 to 480 V, 50/60 Hz
Rated input cur-
rent [A]
*4
HD 2.7 3.9 7.3 11.3 14.2 16.8 23.2 33 43.8 52.3 60.6 77.9
ND 2.7 4.8 7.3 11.3 14.2 16.8 33 43.8 52.3 60.6 77.9 94.3
HHD 1.7 3.1 5.9 8.2 11.3 14.2 17.3 23.2 33 43.8 52.3 60.6
HND 2.7 3.9 7.3 11.3 14.2 16.8 23.2 33 43.8 52.3 60.6 77.9
Rated output voltage Three-phase 380 to 480 V (with AVR)
1 Overview
1-12
M1 Series Standard Type User's Manual (I669)

Table of Contents

Related product manuals