EasyManua.ls Logo

Omron M1 Series - Page 563

Omron M1 Series
808 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter No. Function name Data
Default da-
ta
Unit
E20, E21, E27
Output Terminal [DO1]
Function Selection, Output
Terminal [DO2] Function
Selection, Output Terminal
[ROA, ROB] Function Se-
lection
101: DECF (EN circuit failure detect-
ed)
102: EDM (ST
O (Safe Torque Off)
Performance Monitor)
- -
Wiring Example
Wiring example when EDM is enabled (for compliance with ISO13849-1 PL-e)
 
M
X
+24V
SF2
3G3M1
24V
SF1
DIC
DOC
DO1
o
r
DO2
EDM
System Configuration Example
To attain CAT.3, PLe/SIL3 as an overall system that uses the 3G3M1 Series, a PLe/SIL3 device must
at least be combined into the system.
Test pulse that is input to safety input terminals [SF1] and [SF2] from an external device must be 1 ms
or less.
The following shows an example of a safety interlock that is combined with the 3G3M1 Series.
Model
Applicable standard for system configura-
tion
Certification authority
G9SP
EN ISO13849-1 PL-e Cat4
(IEC61508 SIL3)
TÜV Rheinland
7 Other Functions
7-71
M1 Series Standard Type User's Manual (I669)
7-6 Safety Function
7
7-6-3 Wiring Safety Function for Use

Table of Contents

Related product manuals