Frequency arrival signal 1
(constant speed) “FAR1”
ON
ON ON
ON
Set frequency (1) + E30
Set frequency (2) + E30
Set frequency (1) - E30
Set frequency (2) - E30
Set frequency (1)
Set frequency (2)
Frequency arrival signal 2 “F
AR2”
Frequency Arrival 2 ON Timer E29
Frequency
Arrival 2
ON Timer
E29
Output frequency
Frequency settings changedFrequency settings
Over Set Frequency Arrival Signal (E20, E21, E27 = 2: FDT1, 31:
FDT2)
An ON signal is output when the output frequency becomes equal to or higher than the operation level
(E31/E36) set in the frequency detection, and the signal is turned OFF when the frequency falls below
Frequency Detection Hysteresis Width (FDT1/ FDT2) (E32).
Name Output signal
E20, E21, E27
allocated data
Operation level Hysteresis width
Range: 0.0 to 500.0
Hz
Range: 0.0 to 500.0
Hz
Over set frequency ar-
rival signal 1
FDT1 2 E31 E32
Over set frequency ar-
rival signal 2
FDT2 31 E36 E32
Set frequency
Frequency Detection
Level1 (FDT1/FDT3) (E31),
Frequency Detection Level 2
(FDT2/FDT4) (FDT1/FDT3) (E36)
Frequency Detection Hysteresis
Width (FDT1/ FDT2) (E32)
Cancellation level
Time
Time
Output frequency
ON
Over set frequency
arrival signal 1 “FDT1”
Over set frequency
arrival signal 2 “FDT2”
Set-frequency-only Arrival Signal (E20, E21, E27 = 183: FDT3, 185:
FDT4)
An ON signal is output when the output frequency is within the range of the operation level (E31/E36)
set in the frequency detection, and the signal is turned OFF when the frequency is out of range.
7 Other Functions
7-91
M1 Series Standard Type User's Manual (I669)
7-8 Functions Related to Protection, Warning and Various Output Signals
7
7-8-6 Frequency Arrival Signal (FAR1 to 3, FDT1 to 4, FAR1FDT1)