EasyManuals Logo

Omron M1 Series User Manual

Omron M1 Series
808 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #656 background imageLoading...
Page #656 background image
Parameter No. Function name Data
Default
data
Unit
y14
RS-485 Communication
Baud Rate
0: 2400 bps
1: 4800 bps
2: 9600 bps
3: 19200 bps
4: 38400 bps
5: 57600 bps
6: 76800 bps
7: 115200 bps
2 -
y11
RS-485 Communication
Station No. Selection
1 to 255 1 -
y16
RS-485 Communication
Parity Bit Selection
0: None (Stop bit: 2 bits)
1: Even number parity (Stop bit: 1
bits)
2: Odd number parity (Stop bit: 1 bits)
3: None (Stop bit: 1 bits)
3 -
y12
Operation Selection on
Communication Error
0: Immediately trip with alarm ErP
1: T
rip with alarm ErP after running
for the period specified by timer y003
2: Retry during the period specified
by timer y003. If the retry fails trip with
alarm ErP. If it succeeds continue to
run.
3: Continue to run
11: Trip with alarm ErP after decelera-
tion stop
13: Free run stop
14: Deceleration stop
0 -
y18
RS-485 Communication
Timeout Time
0: Not check of the time-out (OFF)
1 to 60 s
0.0
s
y19
RS-485 Communication
Response Interval Time
0.00 to 1.00 s 0.01 s
y13
RS-485 Error Detection
Timer
0.0 to 60.0 s 2.0 s
y97
Communication Data
Storage Selection
0: Store into nonvolatile memory (Re-
writable times are limited)
1: Write into temporary memory (Re-
writable times are unlimited)
2: Save all data from temporary mem-
ory to nonvolatile memory (After all
data is saved, return to Data 1)
1 -
8 Communications Functions
8-6
M1 Series Standard Type User's Manual (I669)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron M1 Series and is the answer not in the manual?

Omron M1 Series Specifications

General IconGeneral
Input Voltage200-240V AC
Output Voltage3-phase 200 to 240 VAC
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit
CommunicationRS-485, Modbus RTU
EnclosureIP20
Cooling MethodFan Cooled
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m
Frequency Range0.5-400 Hz
Storage Temperature-20°C to +65°C

Related product manuals