8 CIP Message Communications
8-38
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
01 0116 Major or minor revision information in the key segment
does not match the device.
01 0117 Invalid connection point.
01 0118 Invalid configuration format.
01 0119 Connection request failed because there is no controlling
connection currently open.
01 011A Target application cannot support any more connections.
01 011B RPI is smaller than the production inhibit time.
01 0203 Connection cannot be closed because the connection has
timed out.
01 0204 Unconnected_Send service timed out while waiting for a
response.
01 0205 Parameter error in Unconnected_Send service.
01 0206 Message too large for unconnected message service.
01 0207 Unconnected acknowledgement without reply.
01 0301 No buffer memory available.
01 0302 Network bandwidth not available for data.
01 0303 No tag filters available.
01 0304 Not configured to send real-time data.
01 0311 Port that was specified in port segment is not available.
01 0312 Link address that was specified in port segment is not
available.
01 0315 Invalid segment type or segment value in path.
01 0316 Path and connection were not equal when closing the con-
nection.
01 0317 Either the segment is not present or the encoded value in
the network segment is invalid.
01 0318 Link address to self is invalid.
01 0319 Resources on secondary are unavailable.
01 031A Connection is already established.
01 031B Direct connection is already established.
01 031C Others
01 031D Redundant connection mismatch.
01 031E There are no more reception resources available on the
sending module.
01 031F No connection resources exist for the target path.
01 0320-07FF Vendor specific.
General Sta-
tus (hex)
Additional Status (hex) Description