3-23
3 System-defined Variables Related to the Built-in EtherNet/IP Port
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-2 System-defined Variables
3
_EIP_EstbTargetSta
[255]
Normal Target Node
Information
NX-series CPU Units: Gives a list of
nodes that have normally established Eth-
erNet/IP connections for CIP communica-
tions 1.
Array[x] is TRUE:
The connection to the node with a target
node ID of x was established normally.
Array[x] is FALSE:
The connection to the node with a tar-
get node ID of x was not established, or
an error occurred.
NJ-series CPU Units: Gives a list of nodes
that have normally established Ether-
Net/IP connections.
Array[x] is TRUE:
The connection to the node with a target
node ID of x was established normally.
Array[x] is FALSE:
The connection to the node with a tar-
get node ID of x was not established, or
an error occurred.
ARRAY
[0..255] OF
BOOL
TRUE or
FALSE
page 3-53
_EIP1_EstbTargetSta
[255]
CIP Communica-
tions1 Normal Target
Node Information
Gives a list of nodes that have normally
established EtherNet/IP connections for
CIP communications 1.
Array[x] is TRUE:
The connection to the node with a target
node ID of x was established normally.
Array[x] is FALSE:
The connection to the node with a tar-
get node ID of x was not established, or
an error occurred.
Note You can use this system-defined vari-
able only for NX-series CPU Units.
ARRAY
[0..255] OF
BOOL
TRUE or
FALSE
page 3-53
_EIP2_EstbTargetSta
[255]
CIP Communica-
tions2 Normal Target
Node Information
Gives a list of nodes that have normally
established EtherNet/IP connections for
CIP communications 2.
Array[x] is TRUE:
The connection to the node with a target
node ID of x was established normally.
Array[x] is FALSE:
The connection to the node with a tar-
get node ID of x was not established, or
an error occurred.
Note You can use this system-defined vari-
able only for the NX701 CPU Units.
ARRAY
[0..255] OF
BOOL
TRUE or
FALSE
page 3-53
Variable name Meaning Function Data type
Range of
values
Reference