5-15
5
b5-12
Selection of
PID feed-
back signal
loss detec-
tion
0: No detection of a feedback
loss.
1: Detection of a feedback
loss. (feedback under
detection level)
Operation continues
during detection, the fault
output is not operated.
2: Detection of a feedback
loss. (feedback under
detection level)
The motor coasts to stop at
detection, and the fault
output operates.
3: Detection of a feedback
loss. (feedback over detec-
tion level)
Operation continues
during detection, the fault
output is not operated.
4: Detection of a feedback
loss. (feedback over detec-
tion level)
The motor coasts to stop at
detection, and the fault
output operates.
0 to 4 0 No A A A A 1B0H 6-99
Fb Los Det
Sel
b5-13
PID feed-
back loss
detection
level
Sets the PID feedback loss
detection level as a percentage
using the maximum output
frequency as 100%.
0 to 100 0% No A A A A 1B1H 6-99
Fb los Det
Lvl
b5-14
PID feed-
back loss
detection
time
Sets the PID feedback loss
detection time.
0.0 to
25.5
1.0 s No A A A A 1B2H 6-99
Fb los Det
Time
b5-15
PID sleep
function
operation
level
Sets the PID sleep function
start level as a frequency.
0.0 to
150.0
*
0.0 Hz No A A A A 1B3H 6-99
PID Sleep
Level
b5-16
PID sleep
operation
delay time
Sets the delay time until the
PID sleep function starts.
0.0 to
25.5
0.0 s No A A A A 1B4H 6-99
PID Sleep
Time
b5-17
Accel/decel
time for PID
reference
Sets the accel/decel time for
PID reference.
0.0 to
6000.0
0.0 s No A A A A 1B5H 6-99
PID Acc/
Dec Time
b5-18
PID Set-
point Selec-
tion
0: Disabled
1: Enabled
0 to 1 0 No A A A A 1DCH 6-99
PID Set-
point Sel
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display