5-32
5
Motor Setup: E2
E1-11
Mid. out-
put fre-
quency 2
Set only to fine-adjust V/f for the
output range. Normally, this setting
is not required.
E1-11 must be set higher than E1-04.
0.0 to
150.0
*2
0.0 Hz
* 4
No A A A A 30AH 6-113
Mid Fre-
quency B
E1-12
Mid. out-
put fre-
quency
voltage 2
0.0 to
255.0
*1
0.0 V
*4
No A A A A 30BH 6-113
Mid Volt-
age B
E1-13
Base volt-
age
(VBASE)
Sets the output voltage of the base
frequency (E1-06).
0.0 to
255.0
*1
0.0 V
*4
* 5
No A A Q Q 30CH 6-113
Base Volt-
age
* 1. The values are for a 200 V class Inverter. Values for a 400 V class Inverter are double.
* 2. The given setting range is valid if Heavy Duty is selected (C6-01=0, default setting). If Normal Duty 1 or 2 is selected (C6-01=1 or 2) the setting
range will be 0.0 to 400.0 Hz.
* 3. The factory setting will change when the control method is changed. (V/f control factory settings are given.)
* 4. E1-11 and E1-12 are disregarded when set to 0.0.
* 5. E1-13 is set to the same value as E1-05 after autotuning.
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
E2-01
Motor rated
current
Sets the motor rated current.
This set value will become the
reference value for motor pro-
tection and torque limits.
This parameter is an input data
for autotuning.
0.32 to
6.40
* 1
1.90 A
* 2
No Q Q Q Q 30EH
6-51
6-111
Motor Rated
FLA
E2-02
Motor rated
slip
Sets the motor rated slip.
This set value will become the
reference value for the slip
compensation.
This parameter is automati-
cally set during autotuning.
0.00 to
20.00
2.90 Hz
*2
No A A A A 30FH 6-111
Motor Rated
Slip
E2-03
Motor no-
load current
Sets the motor no-load cur-
rent.
This parameter is automati-
cally set during autotuning.
0.00 to
1.89
* 3
1.20 A
*2
No A A A A 310H 6-111
No-Load
Current
E2-04
Number of
motor poles
Sets the number of motor
poles.
This value is an input data for
autotuning.
2 to 48 4 poles No No Q Q Q 311H 6-111
Number of
Poles
E2-05
Motor line-
to-line resis-
tance
Sets the motor phase-to-phase
resistance.
This parameter is automati-
cally set during autotuning.
0.000
to
65.000
9.842 Ω
*2
No A A A A 312H 6-111
Term Resis-
tance
E2-06
Motor leak
inductance
Sets the voltage drop due to
motor leakage inductance as a
percentage of the motor rated
voltage.
This parameter is automati-
cally set during autotuning.
0.0 to
40.0
18.2%
*2
No No No A A 313H 6-111
Leak Induc-
tance
Param
eter
Num-
ber
Name
Description
Set-
ting
Range
Fac-
tory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display