5-41
5
Serial Communications Settings: F6
Param-
eter
Num-
ber
Name
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
Control Methods
MEMO-
BUS
Register
Page
V/f
V/f
with
PG
Open
Loop
Vector
Closed
Loop
Vector
Display
F6-01
Operation
selection
after com-
munications
fault
Sets the stopping method for
communications faults.
0: Deceleration to stop using
the deceleration time in
C1-02
1: Coast to stop
2: Fast stop using the
deceleration time in C1-09
3: Continue operation
0 to 3 1 No A A A A 3A2H -
Comm Bus
Flt Sel
F6-02
Input level
of external
fault from
Communica-
tions Option
Card
0: Always detect
1: Detect during operation
0 or 1 0 No A A A A 3A3H -
EF0 Fault
Detection
F6-03
Stopping
method for
external
fault from
Communica-
tions Option
Card
0: Deceleration to stop using
the deceleration time in
C1-02
1: Coast to stop
2: Fast stop using the
deceleration time in C1-09
3: Continue operation
0 to 3 1 No A A A A 3A4H -
EF0 Fault
Action
F6-04
Trace sam-
pling from
Communica-
tions Option
Card
-
0 to
60000
0NoAAAA3A5H-
Trace Sam-
ple Tim
F6-05
Current
monitor unit
selection
Sets the unit of current moni-
tor
0: Ampere
1: 100%/8192
0 or 1 0 No A A A A 3A6H -
Current Unit
Sel
F6-06
Torque ref-
erence/
torque limit
selection
from com-
munications
option card
0: Torque reference/torque
limit by communications
option disabled.
1: Torque reference/torque
limit by communications
option enabled.
0 or 1 0 No No No No A 3A7H -
Torque Ref/
Lmt Sel
F6-08
Operation
selection
after SI-T
WDT error
Sets the stopping method for
SI-T WDT errors (E5)
0: Deceleration to stop using
the deceleration time in
C1-02
1: Coast to stop
2: Fast stop using the decel-
ration time in C1-09
3: Continue operation
0 to 3 1 No A A A A 3B6H -
SI-T
WDTErr Sel